Revision of threshold luminance levels in tunnels aiming to minimize energy consumption at no cost: Methodology and case studies

Thumbnail
Author
Doulos L.T., Sioutis I., Tsangrassoulis A., Canale L., Faidas K.
Date
2020
Language
en
DOI
10.3390/en13071707
Keyword
Data acquisition
Energy conservation
Energy utilization
Light emitting diodes
Lighting
Lighting fixtures
Switching
Tuning
Tunnels
Continuous dimming
Control techniques
Fine-tuning methods
Optimal controls
Performance evaluation
Real case scenarios
Supervisory control and dataacquisition systems (SCADA)
Tunnel lightings
Luminance
MDPI AG
Metadata display
Abstract
Because of the absence of lighting calculation tools at the initial stage of tunnel design, the lighting systems are usually over-dimensioned, leading to over illumination and increased energy consumption. For this reason, a fine-tuning method for switching lighting stages according to the traffic weighted L20 luminance is proposed at no additional cost. The method was applied in a real -case scenario, where L20 luminance of the access zone at eleven (11) existing tunnels was calculated. The traffic weighted method of CR14380 was used in order to calculate the actual luminance levels for the entrance zone. The new transition zone, which decreases luminance curves, was produced and compared with the existing ones. Thus, a new switching control was proposed and programed for the Supervisory Control and Data Acquisition (SCADA) system of the tunnel. The signals of the corresponding eleven L20 meters for a period of eight days were used and the corresponding annual energy consumptions were calculated using the proposed switching program for each tunnel. The results were compared with a number of scenarios in which the existing lighting system was retrofitted with Lighting Emitting Diodes (LED) luminaires. In these scenarios, the new luminaire arrangement was based not only on the existing luminance demand value for the threshold zone, but also on the newly proposed one with two different control techniques (continuous dimming and 10% step dimming). The fine-tuning method for switching resulted in energy savings between 11% and 54% depending on the tunnel when the scenario of the existing installation at no extra cost was used. Energy savings, when LED luminaires were installed, varied between 57% (for the scenario with existing luminance demand value for the threshold zone and 10% step dimming) and 85% (for the scenario with the new calculated luminance demand and continuous dimming). © 2020 by the authors.
URI
http://hdl.handle.net/11615/73446
Collections
  • Δημοσιεύσεις σε περιοδικά, συνέδρια, κεφάλαια βιβλίων κλπ. [19735]
htmlmap 

 

Browse

All of DSpaceCommunities & CollectionsBy Issue DateAuthorsTitlesSubjectsThis CollectionBy Issue DateAuthorsTitlesSubjects

My Account

LoginRegister (MyDspace)
Help Contact
DepositionAboutHelpContact Us
Choose LanguageAll of DSpace
EnglishΕλληνικά
htmlmap