dc.description.abstract | The Legionella colonization frequency at 385 Greek hotel hot and cold water distribution systems was 20.8%. Legionella contamination was associated with the presence of an oil heater (odds ratio [OR] = 2.04, 95% confidence interval [CI] = 1.12 to 3.70), with the sample temperature (OR = 0.26, 95% CI = 0.1 to 0.5), with seasonal operation (OR = 3.23, 95% CI = 1.52 to 6.87), and with the presence of an independent disinfection system (OR = 0.30, 95% CI = 0.15 to 0.62). The same water temperatures, free-chlorine levels, and pHs differently affect the survival of various Legionella spp. | en |
dc.source | Applied and Environmental Microbiology | en |
dc.source.uri | <Go to ISI>://WOS:000245068900013 | |
dc.subject | PARA-OLYMPIC GAMES | en |
dc.subject | COLONIZATION | en |
dc.subject | Biotechnology & Applied Microbiology | en |
dc.subject | Microbiology | en |
dc.title | Risk factors for contamination of hotel water distribution systems by Legionella species | en |