Control and optimization of the Corona effects and breakdown of small rod-plate air gaps stressed by dc and impulse voltages

Thumbnail
Autore
Maglaras, A. L.; Giannakopoulou, K.; Kousiouris, T. G.; Topalis, F. V.; Katsaros, D. S.; Maglaras, L. A.
Data
2013
DOI
10.1109/ICSD.2013.6619741
Soggetto
Breakdown
capacitance
Corona
impulse
simulation
Control and optimization
Corona onset voltage
Electric current pulse
Rod-plate air gaps
Electric breakdown
Electric corona
Electric grounding
Mostra tutti i dati dell'item
Abstract
In the present paper methods of controlling Corona and breakdown in small rod-plate air gaps are investigated. Combining experimental and simulation-theoretical work, it is resulted that when the rod's diameter is bigger, the gap length larger and the rod is grounded the field is less inhomogeneous. Therefore the value of the dc breakdown voltage without Corona is higher. If Corona occurs then the values of the Corona onset voltage are higher, and the corona effects are not intense. The Corona effects, lead to a rise of the value of the dc breakdown voltage especially when the rod is negatively charged. Moreover an insulated thin barrier, when positioned near the rod increases the breakdown dc voltage to a maximum value, and minimizes the Corona effects. Especially for gaps stressed by impulse voltage the Corona effects, appearing with the form of electric current pulses, are influenced by the same factors with a different way. The values of the breakdown voltage in contrast to what happens with dc voltage are higher when the Corona effects are weaker, depending on the influence of the field's inhomogenity (geometry and effect of grounding). It is also resulted that a resistor connected in series with the gap decreases its maximum charging voltage and increases the value of the breakdown voltage. © 2013 IEEE.
URI
http://hdl.handle.net/11615/30475
Collections
  • Δημοσιεύσεις σε περιοδικά, συνέδρια, κεφάλαια βιβλίων κλπ. [19743]
htmlmap 

 

Ricerca

Tutto DSpaceArchivi & CollezioniData di pubblicazioneAutoriTitoliSoggettiQuesta CollezioneData di pubblicazioneAutoriTitoliSoggetti

My Account

LoginRegistrazione
Help Contact
DepositionAboutHelpContattaci
Choose LanguageTutto DSpace
EnglishΕλληνικά
htmlmap